Filtration Process of DVTP Vacuum Transformer Oil Purifier July 27,2023.

DVTP double stages high Transformer Oil Purifier adopts advanced degassing elements, which can greatly improve the degassing efficiency, adopts advanced photoelectric control defoaming device, and adopts mechanical and electronic control type and overpressure alarm device for oil level control, which can realize automatic operation. The oil inlet and outlet have the function of interchanging, and the oil inlet and outlet can be exchanged at will through the valve control during operation, without disassembling the oil pipe. The use of low-power high-density electric heating elements, with overheating protection system, the Vacuum Transformer Oil Purifier in any case will not cause oil deterioration phenomenon, the whole system without cooling, winter use, no need to replace the filter element without tool disassembly.


Different liquids have different saturated steam pressure, at a temperature of 70 ° C, water begins to boil at about 30000a force, while oil can boil at a low pressure of 5Pa. The saturated vapor pressure of oil is much lower than that of water at the same temperature. Therefore, Vacuum Transformer Oil Filtration Machine by vacuuming the pressure of the liquid surface of the oil is reduced to below the saturated vapor pressure of water, then the water in the oil will be vaporized by scraping and overflow from the oil in the form of steam.


Precautions for Transformer Oil Purifier operation:

1. Vacuum pump work, should pay attention to the oil label display of the oil (oil should be on the oil label line), if found vacuum pump oil more water or too dirty, to replace in time, so as not to affect the service life of the vacuum pump.

2. When the cooler is found to have more memory water during operation, it should be discharged in time.

3. The change in the value of the pressure gauge, in the normal Oil Filtration Process, if the pressure is found to be >0.3Mpa, the filter should be cleaned or replaced in time.

4, the filter screen of the initial filter should be often removed and cleaned, keep clean, so as not to clog and cause insufficient oil or too high pressure. When it is found that the oil intake of the Transformer Oil Filtration Machine is small, it indicates that the impurities of the filter screen of the initial filter increase, and it needs to be cleaned immediately.

5, at any time during the operation of the pump and the corresponding motor running noise is normal, if found abnormal should be immediately excluded, so as not to burn the motor or affect the life of the oil pump.

6, when the Oil Filtration Process is stopped and not used, the vacuum pump oil should be drained and new oil should be injected.